Pemeliharaan Tahunan Pressure Transmitter Area Steam Generation Industri Petrokimia di PT. X

Authors

  • Muhammad Hafiz Politeknik Energi dan Mineral Akamigas
  • Novan Akhiriyanto Politeknik Energi dan Mineral Akamigas

DOI:

https://doi.org/10.33795/elposys.v12i2.6424

Keywords:

Calibration, Pressure Transmitter Calibration, Steam Generation, Zero Calibration, IEC Standards

Abstract

Monitoring steam generation systems in the petrochemical industry is essential because small pressure changes can significantly affect product quality and pose safety risks. This study focuses on calibrating the Endress+Hauser Cerabar M PMC41 pressure Transmitter at PT. X, a leading Indonesian fatty alcohol and oleochemical producer. Calibration was performed to ensure accurate pressure measurement of steam generation processes using a zero calibration technique to correct reading Errors. Measurement data were collected before and after calibration at 0%, 25%, 50%, and 100% pressure levels. The initial Error in pressure measurement was 31.799 bar (4.47%), while the current output Error was 16.76 mA (3.8%). After calibration, these Errors reduced to 30.266 bar (0.72%) and 16.023 mA (0.115%), respectively. These results indicate a significant improvement in the Transmitter’s performance, aligning with the International Electrotechnical Commission (IEC) No. 13B-23 standards. The calibration process effectively minimized measurement Errors, ensuring precise monitoring of pressure parameters in the steam generation system and maintaining operational stability. Accurate pressure control is crucial to optimizing production efficiency and maintaining safety standards at PT. X.

References

P. Meilita, R. G. Lina, Restii, and A. Dhiafakhri, “Industri Petrokimia Indonesia,” Apr. 30, 2019, INA-Rxiv. doi: 10.31227/osf.io/gdxjr.

N. Ninasafitri et al., “Kimia Industri,” May 21, 2024, Yayasan Tri Edukasi Ilmiah. doi: 10.5281/ZENODO.13203126.

D. Susanto, V. A. R. Pratiwi, A. Rosyidah, and I. D. Mahardika, “TEKNIK PEMBANGKIT TENAGA LISTRIK,” 2023.

Salsabila Gina Nursyfa, Ika Yuliyani, and Ratu Fenny Muldiani, “Pengaruh Main Overhaul pada Boiler Terhadap Kinerja Menggunakan Metode Direct,” J. Surya Tek., vol. 11, no. 1, pp. 357–362, Jun. 2024, doi: 10.37859/jst.v11i1.7325.

A. U. Rahmawati, L. Wikendi, Y. Maryanty, and N. K. Yusuf, “ANALISIS PROSES KIMIA DALAM SIKLUS UAP AIR DI PLTU PAITON UNIT 1 DAN 2,” DISTILAT J. Teknol. Separasi, vol. 10, no. 3, pp. 562–571, Sep. 2024, doi: 10.33795/distilat.v10i3.6238.

L. K. Munandar, “MENGENAL JENIS – JENIS SENSOR DAN PEMANFAATANNYA DI DUNIA INDUSTRI,” 2023.

L. A. Fatimah and R. Hidayat, “Analisis Hasil Studi Kasus Kalibrasi Pressure Transmitter dengan Metode Zero Calibration,” ELECTRON J. Ilm. Tek. Elektro, vol. 5, no. 1, pp. 21–29, May 2024, doi: 10.33019/electron.v5i1.109.

E. D. Suminta, “IMPLEMENTASI METODE RELIABILITY CENTERED MAINTENANCE (RCM) II PADA CLOSE COOLING WATER SYSTEM PEMBANGKIT LISTRIK TENAGA UAP,” 2020.

C. Sihombing, P. R. Rumahorbo, and R. Situmorang, “ANALISIS SISTEM INTERLOCK MOTOR FORCE / INDUCED DRAFT FAN PADA BOILER DENGAN PENGENDALIAN DCS DI PT UNILEVER OLEOCHEMICAL INDONESIA,” 2024.

K. O. Purnama, D. Setyaningsing, E. Hambali, and D. Taniwiryono, “PELUANG PALM FATTY ACID DISTILLATE DARI INDUSTRI MINYAK SAWIT DALAM PEMBUATAN MONO-DIGLISERIDA The Opportunities of Palm Fatty Acid Distillate from Palm Oil Industry in Production of Mono-Diglyceride,” Perspektif, vol. 20, no. 1, p. 11, Nov. 2021, doi: 10.21082/psp.v20n1.2021.11-25.

A. Irawan, “Kalibrasi Spektrofotometer Sebagai Penjaminan Mutu Hasil Pengukuran dalam Kegiatan Penelitian dan Pengujian,” Indones. J. Lab., vol. 1, no. 2, pp. 1–9, Apr. 2019.

M. J. Rezky, “TESTING DAN KALIBRASI MESIN CNC ENGRAVER MACH-MILL DENGAN RANGE,” vol. 8, no. 2, 2024.

A. M. Purba, M. F. Fahlevi, and A. M. Simanjuntak, “Analisa Verifikasi Dan Kalibrasi Alat Instrumentasi Level Displacer Interface Di Pt. Domas Agrointi Prima,” Ilm. Tenaga List., vol. 1 (2), pp. 65–74, 2022.

E. A. Prastyo, “Multimeter: Penggunaan dan Cara Mengukur Tegangan, Arus, dan Resistansi - Edukasi Elektronika | Electronics Engineering Solution and Education,” 2024.

Endress, “Process pressure measurement Pressure transmitter with ceramic and metal sensors Overload-resistant and function-monitored With Analog, HART or PROFIBUS PA Electronics,” 2022.

Downloads

Published

2025-06-30

How to Cite

Hafiz, M., & Novan Akhiriyanto. (2025). Pemeliharaan Tahunan Pressure Transmitter Area Steam Generation Industri Petrokimia di PT. X. Elposys: Jurnal Sistem Kelistrikan, 12(2), 126–131. https://doi.org/10.33795/elposys.v12i2.6424